Residual current releases combined with circuit-breakers are used for protection against the effects of leakage currents. These device combinations fulfill the following tasks:
Depending on type the residual current releases protect the following:
These kinds of residual current releases can be attached to the NZM1 and NZM2 circuit-breakers. No auxiliary voltage is required. In the event of a fault, the residual current release trips the circuit-breaker, i.e. the main contacts are opened. The circuit-breaker and the residual current release must be reset to restore the supply.
The main functions and the associated values are shown in the following table.
They can be used in three-phase and single-phase systems.
With 2-pole operation it must be ensured that voltage is applied to both terminals required for test functions.

Test button (T)

NZM1-(4)..., NZM2-4...

+NZM2-4-XFI

NZM1-(4)-XFI
Trip indication is implemented via auxiliary contacts. The NZM2-4-XFI… has fixed contacts. The NZM1(-4)-XFI… allows two M22-K… contact elements from the Moeller RMQ-Titan range to be clipped in.
Contact representation for “not released” [t-head3]
NZM1(-4)-XFI…
NZM2-4-XFI…

