Control circuit devices
LS-Titan® position switches

"Process protection and enhanced personnel protection" with separate signal for door position [t-head1-pg]

LS…ZBZ
   

  • Stop signal
  • Waiting time
  • Process sequence halted
  • Protective device open
  • Product OK

LS…MT-ZBZ, magnet-powered interlock (operating current principle) [t-head1-nnp]

LS-S02-…MT-ZBZ

 

 

 

Position 1Safety contact

Position 2Signalling contact

Position 3Interlocked

Position 4Released

Position 5open

Door closed and interlocked
Voltage on coil (A1, A2)
Safety contact (21-22) closed
Signalling contact (11 - 12) closed
 
Door open
Both contacts in the open position
tamperproof against simple tools
 
 
 
 
Door released
Coil de-energised (A1, A2)
e.g. via zero-speed monitor,
Safety contact (21 – 22) opens
Signalling contact (11 - 12) remains closed
Close door
Signalling contact (11 – 12) closes
 
 
 
 
Door open
Only possible once it is released
Signalling contact (11 - 12) opens.
Interlock door
Apply voltage to coil (A1, A2)
1st actuator interlocked
2nd safety contact (21-22) closes

LS-S11-…MT-ZBZ

 

 

 

Position 1Safety contact

Position 2Signalling contact

Position 3Interlocked

Position 4Released

Position 5open

Door closed and interlocked
Voltage on coil (A1, A2)
Safety contact (21-22) closed
Signalling contact (13-14) open
 
Door open
Safety contact (21 - 22) open
Signalling contact (13-14) closed
 
 
 
 
Releasing of door
Coil de-energised (A1, A2)
e.g. via zero-speed monitor,
Safety contact (21 – 22) opens
Close door
Signalling contact (13 - 14) opens.
 
 
 
 
Door open
Only possible once it is released
Signalling contact (13 - 14) closes.
Interlock door
Apply voltage to coil (A1, A2)
1st actuator interlocked
2nd safety contact (21-22) closes


Imprint © 2009 by Moeller GmbH   Top