Analogue input connections to easy…DA/DC-… or MFD-R…/T… [t-head1-pg]

Setpoint device via separate power supply and potentiometer ≤1 kΩ, e.g. 1 kΩ, 0.25 W

Setpoint device with upstream resistance 1.3 kΩ, 0.25 W, potentiometer 1 kΩ, 0.25 W (value for 24 V DC)

Temperature monitoring via temperature sensor and transducer

Sensor 4 to 20 mA mit resistor 500 Ω
Note
- Pay attention to the differing number and designation of the analogue inputs of each device type.
- Connect the 0 V of the or the MFD-Titan with the 0 V of the power supply of the analogue encoder.
- sensor of 4(0) to 20 mA and a resistance of 500 Ω give the following approx. values:
- Analogue input 0 to 10 V, Resolution 10 Bit, 0 to 1 023.