Contactors and Relays
Control relay easy, Multi Function Display MFD-Titan®

Connection from transistor outputs for easy and MFD-Titan [t-head1-pg]

Position 1 

Contactor coil with zener diode as suppressor, 0.5 A bei 24 V DC

Position 2 

Valve with diode as suppressor,
0.5 A at 24 V DC

Position 3 

Resistor,
0.5 A at 24 V DC

Position 4 

Indicator lamp 3 or 5 W at 24 V DC,
Output dependant upon device types and outputs

Note
When switching off inductive loads the following should be considered:
Suppressed inductances cause less interference in the total electrical system. It is generally recommended to connect the suppressor as close as possible to the inductance.

When the inductances are not suppressed, then :
several inductances must not be switched off at the same time, so that in the worst case the driver block does not overheat. Should, in an emergency stop situation the +24 V DC supply be switched off by another contact and thereby more than one controlled output be switched off, the inductances must have a suppressor.