Network connection [t-head1-pg]
Sockets RJ 45 and plug [t-head3]
Connection layout of socket RJ 45 on easy and MFD-Titan.
Connection layout of plug RJ45 on easy and MFD-Titan.

Cable entry side
8 pole RJ 45, EASY-NT-RJ 45
Layout with EASY-NET [t-head3]
PIN 1; ECAN_H; Data conductor; conductor pair A
PIN 2; ECAN_L; Data conductor; conductor pair A
PIN 3; GND; ground conductor; conductor pair B
PIN 4; SEL_IN; Select conductor; conductor pair B
Configuration of the network cable for EASY-NET [t-head3-col]
The network cable does not need to be screened.
The characteristic impedance of the cable must be 120 Ω.
Note
The minimal operation with easy-NET functions with the conductors ECAN_H, ECAN_L, GND. The SEL_IN conductor is solely for automatic addressing.
Bus terminal resistor [t-head3]
A bus terminal resistor must be connected to the geographical first and last device in the network:
Pre-finished conductors, RJ45 plug on both ends [t-head3]