Contactors and Relays
Control relay easy, Multi Function Display MFD-Titan®

Network connection [t-head1-pg]

Sockets RJ 45 and plug [t-head3]

Connection layout of socket RJ 45 on easy and MFD-Titan.

Connection layout of plug RJ45 on easy and MFD-Titan.

Position 1Cable entry side

8 pole RJ 45, EASY-NT-RJ 45

Layout with EASY-NET [t-head3]

PIN 1; ECAN_H; Data conductor; conductor pair A

PIN 2; ECAN_L; Data conductor; conductor pair A

PIN 3; GND; ground conductor; conductor pair B

PIN 4; SEL_IN; Select conductor; conductor pair B

Configuration of the network cable for EASY-NET [t-head3-col]

The network cable does not need to be screened.

The characteristic impedance of the cable must be 120 Ω.

A
1
ECAN_H
A
2
ECAN_L
B
3
GND (Ground)
B
4
SEL_IN

Note
The minimal operation with easy-NET functions with the conductors ECAN_H, ECAN_L, GND. The SEL_IN conductor is solely for automatic addressing.

Bus terminal resistor [t-head3]

A bus terminal resistor must be connected to the geographical first and last device in the network:

  • Value of the bus terminal resistor 124 Ω,
  • Connect to PIN 1 and PIN 2 of the RJ-45 plug,
  • Connection plug : EASY-NT-R.

Pre-finished conductors, RJ45 plug on both ends [t-head3]

Conductor length [cm]
 
Part reference
   
 
30
 
EASY-NT-30
80
EASY-NT-80
150
EASY-NT-150


Imprint © 2006 by Moeller GmbH   Top