Input/output expansion
[t-head1-pg]
Central expansion, up to 40 I/O [t-head3]
easy700, easy800, MFD(-AC)-CP8… as well as EC4P-200 can be expanded with easy202, easy410, easy618 or easy620. This provides you with up to 24 inputs and 16 outputs. One expansion device per basic unit is possible, → section Central and remote expansion
.
Remote expansion, up to 40 I/O [t-head3]
easy700, easy800, EC4P-200 and MFD-Titan are expanded with easy410, easy618 or easy620 using the EASY200-EASY coupling module. The expansion device can be operated up to 30 m from the basic device. There are a maximum of 24 inputs and 16 outputs available. One expansion device per basic unit is possible, → section Central and remote expansion
.
Networking via
Net, up to 320 I/O [t-head3]
Up to eight stations can be interconnected by expanding the inputs and outputs via easyNet. An expansion device can be added to each easy800, MFD(-AC)-CP8… or EC4P-200. A network length of up to 1 000 m is possible. There are two types of operation:
→ section
Net, “loop through the device” network connection
Networking via CANopen (
Control) [t-head3-col]
easyControl makes it possible to create networks via CANopen. For this the digital or analog I/O expansion modules EC4E… can be used. Another easy expansion module can be then connected to this (e.g. easy410, easy618, easy620). Observe the CANopen specification!