Electronic motor starters and drives
Connection examples, DS4

Pump connection, single direction of rotation [t-head2-pg]

In pump applications the bypass contactor is often required to provide emergency operation capability. This is achieved with a service switch that allows a changeover from soft starter operation to DOL starting through the bypass contactor. In the latter setting the soft starter is fully bypassed. But because the output circuit must not be opened during operation, the interlocks ensure that changeovers take place only after a stop.

Note:
In contrast to simple bypass operation, the bypass contactor must be laid out to AC3 here. For a suitable contactor, see our recommended mains contactor in appendix “Technical data”.

   

Pump [t-head3]

 

Q1: Line protection

Q11: Mains contactor (optional)

Q21: Bypass contactor

Q31: Contactor

F1: Overload relay

F2: Semiconductor fuse for type “2” coordination, in addition to Q1

T1: Semiconductor contactor

M1: Motor

Pump control [t-head3-ls]

Emergency-Stop

Position 1t > t-Stop + 150 ms

Position 2Enable

Position 3Hand

Position 4Auto

Position 5Soft start/soft stop

Position 6RUN

Position 7Bypass