Electronic motor starters and drives
DS4 connection examples

Pump control, single direction of rotation, continuous operation [t-head2-pg]

In pump applications the bypass contactor is often required to provide emergency operation capability. This is achieved with a service switch that allows a changeover from soft starter operation to DOL starting through the bypass contactor. In the latter setting the soft starter is fully bypassed. But because the output circuit must not be opened during operation, the interlocks ensure that changeovers take place only after a stop.

Note

In contrast to simple bypass operation, the bypass contactor must be laid out to AC3 here.

Pump [t-head3]

 
   

Q1: Line protection

Q11: Mains contactor (optional)

Q21: Soft starters

Q22: Bypass contactor

Q31: Motor contactor

F2: Overload relays

F3: Semiconductor fuse for
type 2 coordination, in addition to Q1
(optional)

M1: Motor