The Moeller Wiring Manual
The Power Distribution Concept from Moeller

Low-voltage switchgear assemblies for infrastructure [t-head1-first]

System Range xEnergy [t-head3]

xEnergy is a freely combinable system range for power distribution, specifically for the infrastructure up to 4000 A.

The Moeller system range xEnergy is optimally designed for safe power distribution.

It consists of:

  • Switching and protective devices,
  • the mounting systems,
  • the switchgear cabinet inclusive of planning- and calculation tools.

The system range xEnergy forms the switching and protective devices, the corresponding mounting systems and the switchgear cabinet components into a technical and economic entity.

The optimum mechanical adaptation of the switchgear cabinet components to the Moeller switching devices achieves short installation times and great flexibility.

The type tests of the complete units of switching devices, mounting systems and switchgear cabinet to IEC EN 60439 also ensure a high safety level.

xEnergy is based on a building-block principle consisting of functional modules that fit perfectly together and are type-tested to IEC 60439. The modular system, available from Form 1 to Form 4, is designed to match local installation practices (DIN VDE, CEI, NF, UNE). All the relevant switchgear combinations in any enclosure protection degree up to 4000 A are type-tested.

Product attributes [t-head3-col]

  • Clear segregation into functional areas up to Form 4b
  • Enclosures for combination- and separate mounting,
  • Enclosure protection IP31 or IP55
  • Main busbars at the rear up to 4000 A
  • Main busbars at the top up to 3200 A
  • All components fitted as TTA
  • Mains system types TN-C, TN-C-S, TN-S, TT, IT

Products [t-head3]

 

XPower Panels

  • Incomers/feeders, outgoers or bus-couplers with circuit-breakers NZM4 or IZM up to 4 000 A
  • Fixed mounted or withdrawable
  • 3 or 4 pole circuit-breakers
  • Cable- or busbar trunking connection from top or bottom

 

 

XFixed Panels

  • Outgoers with circuit-breakers PKZ or NZM up to 630 A
  • Incomers/feeders or outgoers with circuit-breakers NZM4 up to 1600 A
  • Fixed mounted or withdrawable (630 to 1600 A)·
  • 3 or 4 pole circuit-breakers
  • Cable connection from top or bottom

 

 

XFixed Panels

  • Outgoers with fuse combination units SASIL up to 630 A, plug-in units, vertically or horizontally fitted
  • Outgoers with fuse-strip units SL up to 630 A, fixed mounted, vertically fitted
  • 3 pole
  • Cable connection from top or bottom

 

 

XGeneral Panels

  • Mounting systems for rail-mounted service installation devices
  • Customized fixed mounted units on mounting plates up to 630 A, e.g. softstarters, frequency inverters, power factor correction
  • Automation engineering
  • Control technology adapter systems xStart

 