The Moeller Wiring Manual
The Power Distribution Concept from Moeller

Arc fault protective system ARCON® [t-head1-pg]

Maximum personnel and system safety, especially during continuous production processes, made possible using the arc-fault protective system ARCON. The system offers protection from 6 to 100 kArms arc fault current.

Detection of the arc faults is by light and current sensors. The evaluation unit responds when light and current signals are present. A tripping signal is applied to the quenching device and to the feeder circuit-breakers. The fault arc is quenched in less than 2 ms. The system can be put back into operation as soon as the fault is eliminated and the quenching device is renewed.

Position 1Current transformer

Position 2Linear light sensor +ARC-SL...

Position 3Electronic evaluation unit (Slave) +ARC-EL3

Position 4Electronic evaluation unit (Master) +ARC-EM

Position 5Quenching device +ARC-AT

ARCON® – Quenching Device [t-head3]

Things happen extremely quickly once the electronic evaluation unit has responded. ARCON® has quenched the fault arc in 2 ms, before it can cause serious damage.


Imprint © 2006 by Moeller GmbH   Top