Fully automatic main transfer switch with automatic reset

Changeover device to DIN VDE 0108 – Power systems and safety power supply in buildings for public gatherings: [t-head1-pg]

Automatic resetting, the phase-monitor is set to:

Pick-up voltage Uon = 0.95 × Un
Drop-out voltage Ub = 0.85 × Uon

Position 1Main supply

Position 2Auxiliary supply

 

Position 3To load

Method of operation [t-head3]

Main switch Q1 is closed first, followed by main switch Q1.1 (auxiliary supply).

Phase monitor K1 is energized via the main supply and immediately energizes contactor relay K2. Normally closed contact K2/21–22 blocks the circuit of Contactor Q12 (auxiliary supply) and normally open contact K2/13–14 closes the circuit of contactor Q11. Contactor Q11 energizes and switches the mains supply on the loads. Contactor Q12 is also interlocked against main supply contactor Q11 via normally closed contact Q11/22–21.