Rated operational currents

Motor operational currents for three-phase motors (standard values for squirrel cage motors) [t-head1-first]

Minimum fuse size for short-circuit protection of three-phase motors [t-head3]

The maximum size is determined by the requirements of the switchgear or overload relay.

The rated motor currents are for standard 1500 r.p.m. motors with normal inner and outer surface cooling.

D.O.L. starting:
Maximum starting current: 6 × rated current Maximum starting time: 5 sec.
/ starting:
Maximum starting current: 2 × rated current Maximum starting time: 15 sec.
Motor overload relay in phase current: set to 0.58 × rated current.

Rated fuse currents for / starting also apply to three-phase motors with slip-ring rotors.

For higher rated currents, starting currents and/or longer starting times, larger fuses will be required.

This table applies to “slow” or “gL” fuses (VDE 0636).

In the case of low-voltage h.b.c. fuses (NH type) with aM characteristics, fuses are to be selected according to their current rating. [t-head3]

Motor rating
230 V
 
400 V
Motor ­operation rated ­current
 
Fuse
 
 
Motor­ operation rated ­ current
 
Fuse
 
 
Direct starting
 
/
Direct starting
 
/
       
kW
 
cos φ
η [%]
A
 
A
 
A
 
A
 
A
 
A
0.06
0.09
0.12
0.18
 
0.7
0.7
0.7
0.7
 
58
60
60
62
 
0.37
0.54
0.72
1.04
 
2
2
4
4
 
2
2
 
0.21
0.31
0.41
0.6
 
2
2
2
2
 
0.25
0.37
0.55
0.75
0.7
0.72
0.75
0.79
62
66
69
74
1.4
2
2.7
3.2
4
6
10
10
2
4
4
4
0.8
1.1
1.5
1.9
4
4
4
6
2
2
2
4
1.1
1.5
2.2
3
0.81
0.81
0.81
0.82
74
74
78
80
4.6
6.3
8.7
11.5
10
16
20
25
6
10
10
16
2.6
3.6
5
6.6
6
6
10
16
4
4
6
10
4
5.5
7.5
11
0.82
0.82
0.82
0.84
83
86
87
87
14.8
19.6
26.4
38
32
32
50
80
16
25
32
40
8.5
11.3
15.2
21.7
20
25
32
40
10
16
16
25
15
18.5
22
30
0.84
0.84
0.84
0.85
88
88
92
92
51
63
71
96
100
125
125
200
63
80
80
100
29.3
36
41
55
63
63
80
100
32
40
50
63
37
45
55
75
0.86
0.86
0.86
0.86
92
93
93
94
117
141
173
233
200
250
250
315
125
160
200
250
68
81
99
134
125
160
200
200
80
100
125
160
90
110
132
160
0.86
0.86
0.87
0.87
94
94
95
95
279
342
401
486
400
500
630
630
315
400
500
630
161
196
231
279
250
315
400
400
200
200
250
315
200
250
315
400
0.87
0.87
0.87
0.88
95
95
96
96
607
800
630
349
437
544
683
500
630
800
1000
400
500
630
800
450
500
560
630
0.88
0.88
0.88
0.88
96
97
97
97
769
1000
800

Motor rating
500 V
 
690 V
Motor ­operation rated ­current
 
Fuse
 
 
Motor ­operation rated ­current
 
Fuse
 
 
 
Direct starting
 
/
 
Direct starting
 
/
           
kW
 
cos φ
η [%]
A
 
A
 
A
 
A
 
A
 
A
0.06
0.09
0.12
0.18
 
0.7
0.7
0.7
0.7
 
58
60
60
62
 
0.17
0.25
0.33
0.48
 
2
2
2
2
 
 
0.12
0.18
0.24
0.35
 
2
2
2
2
 
0.25
0.37
0.55
0.75
0.7
0.72
0.75
0.79
62
66
69
74
0.7
0.9
1.2
1.5
2
2
4
4
2
2
2
0.5
0.7
0.9
1.1
2
2
4
4
2
2
1.1
1.5
2.2
3
0.81
0.81
0.81
0.82
74
74
78
80
2.1
2.9
4
5.3
6
6
10
16
4
4
4
6
1.5
2.1
2.9
3.8
4
6
10
10
2
4
4
4
4
5.5
7.5
11
0.82
0.82
0.82
0.84
83
86
87
87
6.8
9
12.1
17.4
16
20
25
32
10
16
16
20
4.9
6.5
8.8
12.6
16
16
20
25
6
10
10
16
15
18.5
22
30
0.84
0.84
0.84
0.85
88
88
92
92
23.4
28.9
33
44
50
50
63
80
25
32
32
50
17
20.9
23.8
32
32
32
50
63
20
25
25
32
37
45
55
75
0.86
0.86
0.86
0.86
92
93
93
94
54
65
79
107
100
125
160
200
63
80
80
125
39
47
58
78
80
80
100
160
50
63
63
100
90
110
132
160
0.86
0.86
0.87
0.87
94
94
95
95
129
157
184
224
200
250
250
315
160
160
200
250
93
114
134
162
160
200
250
250
100
125
160
200
200
250
315
400
0.87
0.87
0.87
0.88
95
95
96
96
279
349
436
547
400
500
630
800
315
400
500
630
202
253
316
396
315
400
500
630
250
315
400
400
450
500
560
630
0.88
0.88
0.88
0.88
96
97
97
97
615
800
630
446
491
550
618
630
630
800
800
630
630
630
630


Imprint © 2006 by Moeller GmbH   Top