Standards, formulae, tables
Conductors

Wiring and cable entries with cable glands [t-head1-pg]

Metric cable glands to EN 50262 [t-head3]

with 9, 10, 12, 14 or 15 mm long thread.

Cable­ glands
Cable­ entry
 
Hole ­diamter­
 
Cable­ external­ diameter­
 
For use with NYM/NYY cables, 4-core
 
Cable­glands
Type
 
 
 
mm
 
mm
 
mm2
 

  • With lock nut and built-in strain relief
  • IP68 up to 5 bar, polyamide, halogen-free
M12
 
12.5
 
3 –7
 
H03VV-F3 × 0.75
NYM 1 × 2.5
 
V-M12
M16
 
16.5
 
4.5 – 10
 
H05VV-F3 × 1.5
NYM 1 × 16/3 × 1.5
 
V-M16
M20
 
20.5
 
6 – 13
 
H05VV-F4 × 2.5/3 × 4
NYM 5 × 1.5/5 × 2.5
 
V-M20
M25
 
25.5
 
9 – 17
 
H05VV-F5 × 2.5/5 × 4
NYM 5 × 2.5/5 × 6
 
V-M25
M32
 
32.5
 
13 – 21
 
NYM 5 × 10
 
V-M32
M32
 
32.5
 
18 – 25
 
NYM 5 × 16
 
V-M32G1)
M40
 
40.5
 
16 – 28
 
NYM 5 × 16
 
V-M40
M50
 
50.5
 
21 – 35
 
NYM 4 × 35/5 × 25
 
V-M50
M63
 
63.5
 
34 – 48
 
NYM 4 × 35
 
V-M63
1) Does not correspond to EN 50262.

Detailed information on material properties  table.


Imprint © 2009 by Moeller GmbH   Top