Export to the world market and to North America
Fuses for circuits in North America

Selection and application of fuses suitable for circuits (feeder and branch circuits) in North America.

Type or design in:
 
Standards UL, CSA
 
Fuse ­characteristics
 
SCCR
 
Typical values in A
 
 
Fields of application
 
Notes
USA
 
Canada
 
 
 
 
 
 
 
 
 
 
Class H, "Code"
 
Class H, No. 59 "Code"
 
UL 248-6/7, C22.2 248-6/7
 
fast
 
10 kA, 250 VAC
 
0…600
   
Primarily domestic
 
Types H, K and No. 59 “Code” fit the same bases and are therefore interchangeable. There is therefore a risk that they may be incorrectly used! See also note on  K.
10 kA, 600 VAC
Class CC
Class CC
UL 248-4, C22.2 248-4
fast
slow
200 kA, 600 VAC
0.5…30
fast:
 
Protection from resistive and inductive loads.
 
 
Circuits for heating, lighting, feeders and branches for mixed loads.
 
slow:
 
Protection from inductive and highly inductive loads.
 
Circuits for motors, transformers, lighting etc.
Extremely compact design!
Current-limiting to UL/CSA!
Class G
Class G
UL 248-5, C22.2 248-5
fast
slow
100 kA, 480 VAC
21…60
Compact design.
Current-limiting to UL/CSA!
All other fuse types do not fit into bases.
100 kA, 600 VAC
0.5…20
Class J
Class J
HRCI-J
UL 248-8, C22.2 248-8
fast
slow
200 kA, 600 VAC
1…600
Compact design.
Current-limiting to UL/CSA!
All other fuse types do not fit into bases.
Class K
K1, K5
Class K
K1, K5
UL 248-9, C22.2 248-9
fast
slow
50 kA/100 kA/
200 kA,
600VAC
0…600
Not current-limiting to UL/CSA!
In the USA, the K types are therefore being increasingly replaced by the RK types.
Class L
Class L
UL 248-10, C22.2 248-10
fast
slow
200 kA, 600 VAC
601…6000
Current-limiting to UL/CSA!
All other fuse types do not fit into bases.
Class R
RK1, RK5
Class R
HRCI-R RK1, RK5
UL 248-12, C22.2 248-12
fast
slow
50 kA/100 kA/
200 kA,
600VAC
0…600
Current-limiting to UL/CSA!
Types RK1, RK5 and HRCI-R fit the same bases. All other fuse types do not fit into these bases.
RK1 fuses have lower let-through values than RK5.
Class T
Class T
UL 248-15, C22.2 248-15
fast
200 kA, 300 VAC
200 kA, 600 VAC
0…1200
_
Extremely compact design!
Current-limiting to UL/CSA!
All other fuse types do not fit into bases.

The characteristics data and the assigned applications are a rough overview only.

The practice, it is always advisable to find out both this information and the required fusel type from the North American end customer.

The NA fuse types are largely tested and suitable for DC circuits in accordance with UL and CSA.